COLLIN CREEK ASSISTED LIVING CENTER, INC.
6400 CHEYENNE TR, Plano, TX, 75023 · Collin County
State violations cited
2020 · 11 cited
The facility's plan failed to document the contact information for the EMC for the area.
Life Safety CodeCited Sep 9, 2020Corrected Sep 17, 2020
The facility failed to ensure that locking devices on control doors released when the fire alarm or sprinkler system were activated.
Life Safety CodeCited Sep 9, 2020Corrected Dec 15, 2020
The facility failed to ensure that locking devices on control doors released when a switch or button was activated at the monitoring station and at the main staff station.
Life Safety CodeCited Sep 9, 2020Corrected Dec 15, 2020
The facility failed to comply with Chapter 19 of NFPA 101.
Life Safety CodeCited Sep 9, 2020Corrected Sep 17, 2020
The facility failed to ensure the building and structure complied with other applicable chapters of the Life Safety Code, NFPA 101.
Life Safety CodeCited Sep 9, 2020Corrected Oct 15, 2020
The facility failed to ensure fire drills were conducted and documented to be in compliance with licensing standards for assisted living facilities.
Life Safety CodeCited Sep 9, 2020Corrected Sep 30, 2020
The facility failed to provide lighting levels in compliance with licensing standards for assisted living facilities.
Life Safety CodeCited Sep 9, 2020Corrected Oct 15, 2020
The facility failed to provide a written contract with a fire alarm firm to perform inspections, testing, and system maintenance at least every six months.
Life Safety CodeCited Sep 9, 2020Corrected Oct 5, 2020
The facility failed to ensure the smoke detectors were to be tested for sensitivity as required. The facility failed to provide all required fire alarm documentation, including as-built installation drawings, operation and maintenance manuals, and a written sequence of operation, must be available for examination by DADS.
Life Safety CodeCited Sep 9, 2020Corrected Oct 5, 2020
The facility failed to ensure the required sprinkler system was inspected, tested, and maintained in compliance with NFPA 25.
Life Safety CodeCited Sep 9, 2020Corrected Dec 15, 2020
The facility failed to provide and/or maintain a commercial range hood and exhaust system in compliance with NFPA 96.
Life Safety CodeCited Sep 9, 2020Corrected Oct 1, 2020